T-Series Panel/Ceiling Models
OverviewT-Series panel/ceiling models are suitable for mounting at any angle in internal partitions, ceilings, ducts and, with louvred grilles, through external walls. When installed only the louvred grille is visible. The range features a unique speed control pack which enables high, medium or low speed to be preset to suit a specific room size or required duty. T-Series controllers may be used with this model to obtain a choice of speeds, reversible airflow direction and automatic sensor operation. When used with a controller, the speed control pack is removed from the T-Series ventilating unit and fitted into the 3-pin socket in the back of the controller. The Vent-Axia Ecotronic controller gives even greater running economy with its minimum speed setting on 'E' mode and infinitely variable speed control. For this controller the speed control pack remains in the fan. Easy CleaningIntegrated component design allows all parts to be dismantled for cleaning without the use of specialist tools. Accessories | | T-Series Controller | - Three speeds. Choice of extract/intake
- Shutter open, fan Off setting
- Sensor mode. Enables external electro mechanical switches, eg:
Ecotronic, HumidiSwitch, ThermoSwitch and TimeSwitch to control the fan. | |
|
 | | Ecotronic 130 Controller | | All the features of T-Series:- * Infinitely variable speed control * 'E' position for energy saving * Minimum speed adjustment. | |
|
 | | Ecotronic 400 Controller | | For groups of units of any one size up to a total of 400 watts. Do not mix T-Series with Standard Range ventilating units on one controller. | |
|
 | | Air Quality Sensor | | Automatically reacts to the depletion of air quality, sensing tobacco smoke, smells and toilet odours to regulate mechanically ventilated areas such as cinemas, pubs, clubs, restaurants, kitchens, toilets and conference rooms. | |
|
 | | Ambient Response Humidity Sensor | The latest self programming electronic On/Off wall mounted humidity sensor which reacts to any rapid increase in humidity and temperature by switching a Vent-Axia fan ‘On' for rapid removal of moisture laden air, in domestic bathrooms and kitchens. Can be wired into controller "Auto" mode connections. Night time RH increment setback feature suppresses uisance tripping when the humidity level gradually rises as the temperature falls. Features & Benefits: - Ambient operating temp range +5°C to +40°C.
- Changeover relay switch.
| |
|
 | | Ecotronic Humidity Sensor | An adjustable set point, solid state On/Off sensor. A pullcord provides manual override, indicated by lamp. Adjustable from 65 to 90%RH. Can be wired into controller "Auto" mode connections. Incorporates changeover switch to select low/high speed. Features & Benefits: - Ambient operating temp range 0°C to +40°C.
- BEAB Approved.
- Dimensions: 87 x 87 x 33mm (H x W x D).
- Maximum switching load 1 amp inductive.
- Pullcord override indicated by lamp.
- Setting Range: 65% - 90%RH.
| |
|
ShutterWith energy saving in mind TX models are supplied complete with an integral instantaneous automatic louvre shutter concealed behind the interior grille. It will operate on both intake and extract and at any angle of mounting. The shutter is electronically controlled by an actuator with a damped action giving quiet instant operation during instant opening and closing. The interlocking edges of the shutter blades provide maximum backdraught protection. When the ventilating unit is used with a T-Series controller, the shutter can be set open with the fan motor switched Off to provide natural ventilation without the security risk of an open window. TL models do not have a shutter. They are suitable for certain ducted applications, room to room systems and where there is a need for ventilation of specialised equipment. The TL model will also provide natural ventilation where required when the unit is switched Off. ElectricalSuitable for operation in ambient temperatures from -40°C to +50°C. Fitted with self resetting Standard Thermal Overload Protection (S.T.O.P). Supply voltage: 220-240V/1/50Hz (120V/1/60 Hz).
| Unit size | 6 |
|---|
| Type | TX6PL | TL6PL | | Stock Ref. No. | W16 16 10 | W26 16 10 | | Amps @ 240V | 0.24 | 0.21 | | Extract Performance m³/h | Low | 295 | | Extract Performance m³/h | Med | 380 | | Extract Performance m³/h | High | 435 | | Watts (high) | 45 | 40 | | dB(A) (med) @ 3m | 41 | | Shutter (TX only) | Instant | | Surface Controllers | T-Series Type TSC | W36 11 19 | | Surface Controllers | Ecotronic 130 | W30 01 20 | | Surface Controllers | Ecotronic 400 | W36 23 20 | | Surface Controllers | Time Switch TTC | W36 13 10 |
| Unit size | 7 |
|---|
| Type | TX7PL | TL7PL | | Stock Ref. No. | W16 26 10 | W26 26 10 | | Amps @ 240V | 0.24 | 0.21 | | Extract Performance m³/h | Low | 365 | | Extract Performance m³/h | Med | 480 | | Extract Performance m³/h | High | 585 | | Watts (high) | 46 | 41 | | dB(A) (med) @ 3m | 37 | | Shutter (TX only) | Instant | | Surface Controllers | T-Series Type TSC | W36 11 19 | | Surface Controllers | Ecotronic 130 | W30 01 20 | | Surface Controllers | Ecotronic 400 | W36 23 20 | | Surface Controllers | Time Switch TTC | W36 13 10 |
| Unit size | 9 |
|---|
| Type | TX9PL | TL9PL | | Stock Ref. No. | W16 36 10 | W26 36 10 | | Amps @ 240V | 0.42 | 0.39 | | Extract Performance m³/h | Low | 565 | | Extract Performance m³/h | Med | 830 | | Extract Performance m³/h | High | 960 | | Watts (high) | 80 | 75 | | dB(A) (med) @ 3m | 43 | | Shutter (TX only) | Instant | | Surface Controllers | T-Series Type TSC | W36 11 19 | | Surface Controllers | Ecotronic 130 | W30 01 20 | | Surface Controllers | Ecotronic 400 | W36 23 20 | | Surface Controllers | Time Switch TTC | W36 13 10 |
| Unit size | 12 |
|---|
| Type | TX12PL | TL12PL | | Stock Ref. No. | W16 46 10 | W26 46 10 | | Amps @ 240V | 0.51 | 0.48 | | Extract Performance m³/h | Low | 1270 | | Extract Performance m³/h | Med | 1640 | | Extract Performance m³/h | High | 1885 | | Watts (high) | 105 | 100 | | dB(A) (med) @ 3m | 44 | | Shutter (TX only) | Instant | | Surface Controllers | T-Series Type TSC | W36 11 19 | | Surface Controllers | Ecotronic 130 | W30 01 20 | | Surface Controllers | Ecotronic 400 | W36 23 20 | | Surface Controllers | Time Switch TTC | W36 13 10 |
 Dimensions
| Size | 6 (150mm) | 7 (190mm) | 9 (230mm) | 12 (300mm) |
|---|
| A | 310 | 352 | 391 | 470 | | B | 303 | 345 | 388 | 467 | | C | 117 | 117 | 129 | 152 | | D | 32 | 32 | 39 | 41 | | E | 220 | 258 | 302 | 378 | | F | 226 | 265 | 304 | 381 | | GØ | 180 | 218 | 255 | 334 | | HØ | 171 | 210 | 247 | 325 | | J | 267 | 306 | 345 | 422 | | K | 231 | 270 | 309 | 386 | | L | 244 | 282 | 326 | 402 | | M | 85 | 104 | 126 | 164 | | Weight (kg) | 3.50 | 3.82 | 5.13 | 7.44 |
|