DETAILS
150MM IN-LINE ELECTRICAL DUCT HEATER 1200 WATT
Product Details:
Inline Duct heater with spigot connection for standard spiral ducts, manufactured from Aluzinc-coated sheet steel with a heating element in stainless steel. The duct heater has integral overheating protection with a manual reset function.
The duct heater has rubber seals on the connecting spigots. Suitable for control by room thermostat or Pulser.
The minimum air volume is based on a minimum air velocity of 1.5 m/s. These inline duct heaters are designed for a maximum output air temperature of 50°C.
The ductwork heater units can be installed in a horizontal or vertical duct. In horizontal ductwork, the connection box should be installed facing upwards or rotated 90° to one side. Installation with the connection box facing downwards is not allowed. -
TECHNICAL
Technical Specifications
Made to order Yes Product Category Duct Heaters Round System (mm) 150 Product Type Duct Heater Product Group Metal Ducting Product Variety 1200W 230V 1 Phase Economy Delivery Not Eligible Next Day Delivery Not Eligible Quick Search: QS34 -
REVIEWS
-
Q & A
Product Questions
Questions and Answers, do you need more information about this product?
Ask a QuestionYour question will be sent to a member of our team. We'll email you the answer and post it on this page. If your question is about an order you already placed, please use our Contact Form to reach the customer service team.
#1Duct heater controlHi. Am intertested in getting one of these for my MVHR system. Can you provide any information on how they can be controlled by a room thermostat.
Question by Jeff, 05-05-2015Hello Jeff
I will be sending you a separate e-mail in response to your question.
Replied by i-sells, 06-05-2015#2InstallWould this heater be suitable in a domestic situation. Bathroom approx. 50 cubic metres.
Question by Harry Stenhouse, H Stenhouse Electrical, 01-03-2016Hello Harry
Thank you for your question. For me to advise please could you tell me what your application is please.
Kind Regards
Anita
0208 463 9683
Replied by i-sells, 03-03-2016#3Room thermostat to inline heater?Hi. Please advise on above (on MVHR). Presumably just put into live feed to heater? Thanks, Peter F (recent customer)
Question by Peter Furlong, 01-05-2016Hi Peter,
Please see these Wiring Diagrams for the inline duct heater. It should point you in the right direction.
Also, please note that you should always get a qualified electrician for fitting and wiring electrical units.Hope that helps!Replied by i-sells, 05-05-2016#4controlHi please could you confirm how this can be controlled to maintain a room temp when using in an mvhr installation
Question by ben, 21-01-2017Hi Ben
This item is available as a kit with its thermostat and can be found by entering QS4353 into the quick search bar.Replied by i-sells, 23-01-2017#5Paint booth heatingPlease call me. We want to heat the air in our paint booth and are hoping that this duct heater is the way to go
Question by Jonathan Allen, 19-09-2017Hi Jonathan I called Friday and have left a message with a return number 07956 818138
Replied by i-sells, 22-09-2017#6Thermostat controller installationHi. I'm also interested into buying one duct heater. Yet, I'd like to have information on how to control it with a thermostat (no kit). Can you help me please ?
Question by Valentin Guichet, 16-11-2017Hello Valentin
There is a thermostat and ducting kit available (search QS4353)We also have a datasheet with the various sized heaters and the relevant thermostat controllers, however this format will not allow the attachment so I will forward in a separate e-mailReplied by i-sells, 20-11-2017#7dimensionsTight installation - what are the overall dimensions, please?
Question by Douglas Fraser, 08-12-2017Hello Douglas
Thank you for your question. The measurements for the heater are below. If I can help any further please do not hesitate to contact me.Overall measurement is 375mm from end to end of the box the measurement is 278mm and the spigot width is 42mmKind RegardsAnitaReplied by i-sells, 08-12-2017#8suitabilityIs this model suitable for a bathroom of around 9 sqr mtrs? Is the motor considered noisy for such application?
Question by Joseph Busuttil, 18-01-2018Hello Joseph
The product to which you are referring is a duct heater designed to warm air as it passes through an air input duct of a ventilation system. We would not recommend this is used for a bathroom as we do not recommend input or supply air to bathrooms as they should have extraction for the dispersal of water vapour.Replied by i-sells, 18-01-2018#9Heater controlGood afternoon, how is the temp set and controlled on this unit. Also can it be controlled via air flow switch
Question by James Darlison, 04-10-2022Hello James
Thank you for your question. The duct heater is designed to operate on single phase, two phase or three phase alternating current and comes in a varietyof versions with, or without, built-in control equipment. The duct heater must be connected to the mains supply with a fixed installed round cable. Appropriate cable glands mustbe used to retain the electrical protection class. Duct heater versions CBMF, has a built-in electronic interlocking airflow sensor that ensures that the heating elementswill not actuate, unless there is an appropriate airflow through the duct heater. The electronic interlocking device is set foran airflow limit of approximately 1.5 m/s. The inlet air must be filtered to reduce the risk of contamination of the airflowsensor A multi pole switch must be included in the fixed installation. The installation must be carried out by an authorized electrician. The heater is S-marked, CE-marked, EMC-marked and designed in accordance with the following standards:SEMKO 111 FA 1982 / / EN 61000-6-2. The duct heater is equipped with two overheating cut-outs (of which one is manual reset), to prevent overheating whenthe airflow is too low or in case of a fault in the system. A drawing must be attached inside the fuse box or on the wall of the service room. The drawing shows the rating of theduct heater and its location in the building, together with information about the measures to be taken if the overheatingcut-outs is activated.10. Since the sensor circuitry, for heaters type CBM and CBMF, is not galvanic separated from the power supply, care must betaken when the sensor are connected due to the mains voltage level.11.. Duct heater versions CB and CBM,EN 60335-1 / EN 60335-2-30 / EN 61000-6-3 / EN 61000-3 This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities,or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of theappliance by a person responsible for their safety. Furthermore, it must notbe possible to switch off the associated fan unless the power supply to the heater has been turned off in advance or turnedoff at the same time. The air speed through the heater must be at least 1.5 m/I hope this has answered your questions but if you require any further help please do not hesitate to come back to meKind RegardsAnitaReplied by i-sells, 06-10-2022 -
DELIVERY
Delivery: You'll receive in: Cost Min Order Free Delivery 3 to 5 Days FREE £100 Standard 2 to 4 Days £4.99 - Express Courier Next day+ £9.95 Any View Full Delivery Info
FREE Delivery for orders over £100 inc VAT.
+ Order before noon for Next Working Day Delivery for items in stock
Excludes Highlands, Islands, and Certain Postcodes.
Please Note: Ducting tubes over 200mm in diameter and 3 metres in length may incur additional shipping charges.